4 Reasons You Can't Mix R22 and R407C Refrigerant
Last Updated: November 1, 2026
Quick Summary
No, you cannot mix R22 and R407C. They are different refrigerants with different chemistries, oils, and pressure behavior, and no manufacturer approves mixing them. Mixing is not the same as retrofitting, which is a controlled process.
R-407C is a three-part zeotropic blend with roughly 7-10 °F temperature glide, while R-22 is a single-component refrigerant.
R-22 systems typically run mineral oil, but R-407C needs POE oil, so many retrofits require an oil change.
Charge R-407C as a liquid by weight, since pulling vapor can skew the blend ratio.
If R-407C was already added to an R-22 system, recover the mixed charge and label it as mixed.
A proper retrofit includes recovery, filter-drier replacement, deep evacuation, and a leak check before charging.
Table of Contents
Can You Mix R22 and R407C? The Short Answer
No, you cannot mix R22 and R407C. They are different refrigerants with different chemistries, oils, and pressure behavior. Pouring one into a system charged with the other creates a blend nobody designed, and no manufacturer approves it.
Mixing is not the same as retrofitting. A retrofit is a controlled process; mixing is what happens when someone tops off an R-22 system with whatever cylinder is on the truck.
What Happens If You Mix Refrigerants in a Running System
Mixing refrigerants in a running system can degrade performance and put the compressor at risk. Pressures can drift and the lubricant chemistry can turn against you.
Pressures no longer match the label. The system was designed around one refrigerant's pressure-temperature curve.
Oil compatibility breaks down. R-22 systems typically run mineral oil; R-407C needs POE oil.
The charge becomes unknown. You cannot weigh in a correct charge for an unidentifiable blend.
A common mistake is chasing a "low charge" symptom on a contaminated system and adding more refrigerant, which makes the problem worse.
The Blend Problem: R-407C Is Not a Single Refrigerant
R-407C is a blend of three components that behave differently in the system, which makes mixing messy.
Because R-407C is a blend, it has temperature glide: it boils and condenses across a small temperature range instead of at one fixed point, unlike a pure refrigerant like R-22.
That is why you charge R-407C as a liquid.
Add R-22 into that blend and you have changed the recipe entirely. No chart covers it. No manufacturer supports it.
If R-407C Was Already Added to an R-22 System
If R-407C was already added to an R-22 system, stop and plan a full recovery. Do not top it off again. It is contaminated, and the only correct path is to recover the mixed charge, deal with the oil, and decide whether to retrofit properly or replace the equipment.
Stop adding refrigerant immediately.
Recover the mixed charge into a dedicated recovery cylinder. Label it as mixed.
Do not reuse that recovered mix in another system.
Assess the oil. If R-407C ran in a mineral oil system, the oil needs attention.
Check for leaks before you recharge anything.
A mixed charge sold or reused as "R-22" spreads contamination to the next customer's system. Keep mixed refrigerant separate and clearly labeled.
R-22 vs. R-407C: Differences That Decide Compatibility
R-22 and R-407C differ in chemistry, oil preference, pressure behavior, and blend characteristics, and those differences decide whether a system can be converted at all. R-22 is a single-component hydrochlorofluorocarbon (HCFC).
NathansHVAC
Feature | R-22 | R-407C |
Type | Single component (HCFC) | Three-part zeotropic blend (HFC) |
Oil typically used | Mineral oil (or alkylbenzene) | POE oil |
Temperature glide | None (pure refrigerant) | Yes, roughly 7-10 °F at typical evaporating conditions |
Charging method | Vapor or liquid | Liquid only, by weight |
Typical evaporating pressure at 40 °F | About 68-70 psig | About 60-65 psig |
Typical condensing pressure at 110 °F | About 225-230 psig | About 240-250 psig |
Regulatory status | Phased out for new equipment; production and import restricted | Current replacement option |
Those rows explain most retrofit headaches. The oil difference alone forces an oil change in many systems. The glide means you charge by liquid and by weight, and you must account for it when setting superheat or subcooling targets.
Why the Pressure Curve Matters More Than the Label
A system is designed around one refrigerant's pressure-temperature curve, and R-22 and R-407C do not share it. At a 40 °F evaporator, R-22 sits at roughly 68-70 psig while R-407C sits closer to 60-65 psig.
A technician who charges R-407C to an R-22 system's old pressure target will overcharge or undercharge and never know it from the gauge alone. Charge by weight to the manufacturer's retrofit specification, then verify with glide-adjusted superheat or subcooling targets.
The Glide Effect in Plain Terms
Glide has two practical consequences. First, you charge R-407C as a liquid; pulling vapor off the top of the cylinder can skew the mixture and lose the blend ratio because the components have different volatilities. Second, when measuring superheat or subcooling, use the blend's bubble and dew points rather than a single saturation temperature, or you will misdiagnose the charge.
The Regulatory Side
R-22 production and import in the United States are restricted under the EPA's phaseout rules for ozone-depleting substances, and supply can be unpredictable. You can read the EPA phaseout rules for ozone-depleting refrigerants for the official details on handling and supply. R-407C, as an HFC blend, is not an ozone-depleting substance, but it is still subject to refrigerant handling rules under EPA Section 608, including recovery rather than venting.
Key Takeaway R-22 and R-407C are not interchangeable at the gauge. Different pressure curves, a 7-10 °F glide, and a different oil mean a conversion has to be engineered, not improvised.
R407C Drop-In Replacement for R22: What the Label Really Means
R-407C is often sold as an R407C drop-in replacement for R22, but "drop-in" is marketing shorthand, not a technical promise. A true drop-in would mean you recover the old charge, add the new refrigerant, and change nothing else. That is not how R-407C works in most systems, and the reason is mechanical, not semantic.
Why 'Drop-In' Cannot Be Literal
A literal drop-in refrigerant would have to match the original on the pressure-temperature curve, oil compatibility, and metering behavior at once. R-407C matches none of them exactly: its pressure curve sits lower on the evaporator and higher on the condenser than R-22's, it needs POE oil where many R-22 systems run mineral oil, and its glide means the metering device sees a different effective saturation temperature than it was set up for.
When a supplier calls R-407C a drop-in, they usually mean it is compatible with many R-22 systems after proper preparation. That is a real and useful claim, but not the same as "no changes required."
What a Realistic Retrofit Actually Involves
A realistic R-407C retrofit on an R-22 system typically includes:
Recovery of the existing charge. The old R-22 is recovered, not vented, and handled under applicable refrigerant rules.
Oil assessment or replacement. If the system runs mineral oil, the oil is drained and replaced with POE, or the manufacturer's approved additive procedure is followed. Residual mineral oil does not circulate well with R-407C.
Filter-drier replacement. A new drier captures moisture and acid. POE oil is hygroscopic, so moisture control becomes more critical.
That list is why the label is misleading. A job that skips the oil, the drier, or the evacuation is not a retrofit. It is a contamination event waiting to happen.
How to Judge Whether a System Is a Good Candidate
The systems that convert most cleanly tend to share a few traits:
The compressor is healthy and rated for the new refrigerant and oil. A retrofit on a weak compressor just delays a replacement.
The leak history is acceptable. A system that has been losing charge repeatedly is a poor candidate for any conversion.
The metering device can be adjusted or replaced to match R-407C. A sealed, non-adjustable valve with no approved replacement is a red flag.
The retrofit procedure matters more than the refrigerant itself. A careful conversion on a sound system beats a sloppy one on a great refrigerant every time.
Watch Out If a system has already been topped off with R-407C on top of R-22, it is not converted. It is contaminated. The correct next step is recovery of the mixed charge and an assessment by a qualified technician, not another top-off.
Planning an R22 to R407C Retrofit the Right Way
A proper R22 to R407C retrofit is a sequence, not a single service call. Skip a step and you inherit a problem that shows up months later.

Before you touch the system, confirm three things: the equipment is mechanically sound, the leak history is acceptable, and the owner understands the trade-offs. A retrofit on an already-weak compressor just delays a replacement.
Recovery, Evacuation, and the Filter-Drier Swap
Recovery comes first. Federal rules under EPA Section 608 refrigerant handling requirements govern who can handle refrigerants and how they must be recovered.
Next, replace the filter-drier. This is not optional.
Then evacuate the system to a deep vacuum and hold it to confirm there are no leaks.
Only after a clean, holding vacuum do you charge. Charge R-407C as a liquid, by weight, to the manufacturer's spec.
Metering Device and Compressor Checks
The metering device decides how well the retrofit performs. A TXV set up for R-22 may not match R-407C's behavior. Check whether the valve is adjustable or needs a replacement power head.
Compressor compatibility is the other gate.
Also check the start components. A system that was marginal on R-22 may show hard start behavior after conversion. Test it under load before you call the job done.
R407C Retrofit Oil Requirements: Mineral Oil vs. POE
R-407C retrofit oil requirements come down to one rule: R-407C does not circulate well with mineral oil. R-407C needs polyolester oil, usually called POE oil (Effect of Lubricant Contamination on the Performance and Reliability of Heat Pumps...).
Why the switch matters:
Mineral oil and R-407C do not mix well. Oil that does not return to the compressor leaves it running dry.
POE holds moisture. That makes a deep vacuum and a good filter-drier even more important.
Residual mineral oil is a problem. In many retrofits, the old oil has to be drained and replaced with POE.
Some technicians try to avoid the oil change with an additive. That can work in limited cases, but it is not a substitute for following the equipment manufacturer's retrofit guidance.
Repair, Retrofit, or Replace: A Decision Framework
Repair, retrofit, or replace is the decision that actually matters, and it should come before you buy a single cylinder.
Situation | Best Move | Why |
Small leak, strong compressor, owner keeping the system | Repair and recharge | Lowest cost, system still sound |
Sound system, long-term owner, R-22 supply is a problem | Full retrofit to R-407C | Ends the R-22 supply headache |
Weak compressor or repeated leaks | Replace the system | Retrofit money goes to waste |
Mixed charge already in the system | Recover, then decide | Contamination changes the math |
A retrofit is worth it when the equipment has life left in it and the owner plans to keep it.
Quoting a retrofit on a system with a known compressor problem is a callback waiting to happen. Settle the compressor question first.
Ordering R-407C and Retrofit Supplies for Your Next Job
Getting the right supplies in one order can save a second trip. Best Refrigerant offers refrigerant products for retrofit work, with same-day shipping on weekday orders.
When you are ready to convert a system, you can shop our store for R407C refrigerant. We keep hundreds of products in stock, and we carry legacy refrigerants.
Frequently Asked Questions
Can you mix R22 and R407C in the same system?
No. R-22 is a single-component refrigerant, while R-407C is a three-part blend of R-32, R-125, and R-134a. Adding R-407C on top of an R-22 charge creates a mixture with unknown pressure and capacity behavior, and the two use different lubricants. The system will not run to the manufacturer's specifications, and the resulting blend cannot be recovered and reused. The correct approach is full recovery of the existing charge before any conversion work begins.
Can you use R407C as a drop-in replacement for R22?
R-407C is often marketed as a drop-in, but it is not a true drop-in. It is a near-azeotropic blend with temperature glide, so it must be charged as a liquid by weight, never as vapor. An R22 to R407C retrofit also requires removing the mineral oil and installing POE lubricant, replacing the filter-drier, and confirming the metering device and compressor are rated for R-407C. Skipping those steps is what turns a retrofit into a compressor failure.
What happens if R22 and R407C are mixed by mistake?
The system runs on a refrigerant blend nobody designed it for. Capacity and operating pressure drift from spec, the compressor is lubricated with the wrong oil, and moisture control becomes unreliable. You cannot separate the two gases again, so the entire charge has to be recovered as contaminated refrigerant and handled properly. After that, the system needs a full evacuation, a new filter-drier, and a fresh charge of a single refrigerant.
What are the R407C retrofit oil requirements?
R-407C does not circulate well with the mineral oil used in most R-22 systems, so the retrofit calls for polyolester (POE) oil. In practice that means draining the mineral oil, flushing where the manufacturer allows it, and charging the compressor with the POE grade listed on its nameplate. POE absorbs moisture quickly, so keep containers sealed, pull a deep vacuum, and replace the filter-drier as part of the same job.
Mixing R22 and R407C is the one shortcut that always costs more than it saves. If you are planning a proper retrofit, Best Refrigerant can get the refrigerant and supplies to your shop fast, with hundreds of products in stock, same-day shipping on weekday orders, and packaging built to protect heavy cylinders in transit. Get started with Best Refrigerant and keep your next conversion on schedule.